Bug 11168 - doesn-t work with powerware 9120
Summary: doesn-t work with powerware 9120
Status: CLOSED FIXED
Alias: None
Product: Sisyphus
Classification: Development
Component: nut-driver (show other bugs)
Version: unstable
Hardware: all Linux
: P2 normal
Assignee: Michael Shigorin
QA Contact: qa-sisyphus
URL:
Keywords:
Depends on:
Blocks:
 
Reported: 2007-03-21 14:49 MSK by Alexander Volkov
Modified: 2007-05-26 14:51 MSD (History)
1 user (show)

See Also:


Attachments

Note You need to log in before you can comment on or make changes to this bug.
Description Alexander Volkov 2007-03-21 14:49:15 MSK
ups.conf:
[PW9120]
    driver = upscode2
    port   = /dev/ttyS0
    desc   = "Powerware UPS model 9120"
    manufacturer = Powerware
    input_timeout = 10
------------------
#service upsdrv start
Starting UPS drivers: Bad response to UPTP "":
Bad response to UPTP "":
Network UPS Tools - UPS driver controller 2.0.2
Startup timer elapsed, continuing...
Это с родным кабелем. LanSafe под виндой с ним работает.
пробовал перепаять кабель как указано в доке - те же грабли, вид сбоку.
Comment 1 Alexander Volkov 2007-03-21 15:02:58 MSK
попробовал сменить драйвер на bcmxcp:
Mar 21 14:56:54 xeon upsdrvctl: Shutdown delay =  120 seconds
Mar 21 14:56:54 xeon bcmxcp[25237]: Startup successful
Mar 21 14:56:54 xeon upsdrvctl: Network UPS Tools - UPS driver controller 2.0.2
Mar 21 14:56:54 xeon upsdrv: Starting UPS drivers: succeeded
Mar 21 14:56:57 xeon bcmxcp[25237]: Communications with UPS lost: checksum 
error!
Mar 21 14:56:58 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(PW_COMMAND_START_BYTE): -1
!!!
Mar 21 14:56:58 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(Request command): 10!!!
Mar 21 14:56:59 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(PW_COMMAND_START_BYTE): -1
!!!
Mar 21 14:56:59 xeon bcmxcp[25237]: Communications with UPS re-established
Mar 21 14:57:10 xeon smbd[25249]: [2007/03/21 14:57:10, 0] lib/
util_sock.c:write_data(562)
Mar 21 14:57:10 xeon smbd[25249]:   write_data: write failure in writing to 
client 192.168.2.100. Error Con
nection reset by peer
Mar 21 14:57:10 xeon smbd[25249]: [2007/03/21 14:57:10, 0] lib/
util_sock.c:send_smb(769)
Mar 21 14:57:10 xeon smbd[25249]:   Error writing 4 bytes to client. -1. 
(Connection reset by peer)
Mar 21 14:57:10 xeon bcmxcp[25237]: Communications with UPS lost: Not the right 
sequence received c!!!
Mar 21 14:57:10 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(PW_COMMAND_START_BYTE): -1
!!!
Mar 21 14:57:10 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(Request command): 5!!!
Mar 21 14:57:11 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(checksum): ffffffff!!!
Mar 21 14:57:11 xeon bcmxcp[25237]: Communications with UPS re-established
Mar 21 14:57:24 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(PW_COMMAND_START_BYTE): -1
!!!
Mar 21 14:57:24 xeon bcmxcp[25237]: Communications with UPS lost: Receive error 
(PW_COMMAND_START_BYTE): -1
!!!
и этим лог забивается...
Comment 2 Alexander Volkov 2007-03-21 15:38:19 MSK
a bcmxcp_usb у нас отсутствует :(
Comment 3 Alexander Volkov 2007-03-21 15:45:36 MSK
google подсказывает, что староват драйвер
Network UPS Tools - BCMXCP UPS driver 0.08 (2.0.2)

http://www.mail-archive.com/nut-upsuser@lists.alioth.debian.org/msg00015.html

Может, все-таки собрать новую версию? Раздают уже 2.0.5
Comment 4 Dmitry V. Levin 2007-04-13 18:30:39 MSD
Проверьте 2.0.5-alt2.
Comment 5 Dmitry V. Levin 2007-04-15 03:43:15 MSD
bcmxcp_usb у нас теперь присутствует.
будут проблемы - переоткройте.
Comment 6 Alexander Volkov 2007-04-16 09:04:16 MSD
Работает!
Comment 7 Michael Shigorin 2007-05-24 17:57:29 MSD
Для истории (тоже Powerware 9120; на 2.0.5-alt2 из 4.0):

# service upsdrv start
Starting UPS drivers: 
Communications with UPS lost: Error executing command
Communications with UPS lost: Error executing command
Communications with UPS lost: Error executing command
Communications with UPS lost: Error executing command
Communications with UPS lost: Error executing command
Network UPS Tools - BCMXCP UPS driver 0.11 (2.0.5)

Can't find the UPS on port /dev/ttyS0!
Driver failed to start (exit status=1)
Network UPS Tools - UPS driver controller 2.0.5
                                                                               
                                                   [FAILED]

May 24 16:13:30 localhost upsdrvctl: Network UPS Tools - BCMXCP UPS driver 0.11
(2.0.5)
May 24 16:13:30 localhost upsdrvctl: Can't find the UPS on port /dev/ttyS0!
May 24 16:13:30 localhost upsdrvctl: Driver failed to start (exit status=1)
May 24 16:13:30 localhost upsdrvctl: Network UPS Tools - UPS driver controller 2.0.5

С upscode2 -- как и у тебя выше, с bcmxcp_usb:

Starting UPS drivers: Network UPS Tools - BCMXCP UPS driver 0.11 (2.0.5)

Communications with UPS lost: Error executing command
Could not communicate with the ups: Resource temporarily unavailable
Driver failed to start (exit status=1)
Network UPS Tools - UPS driver controller 2.0.5
                                                                               
                                                   [FAILED]

Можешь показать этот кусочек ups.conf, с которым работает?  Потом придётся
вешать багу на alterator-nut или nut, чтобы поправить рекомендованный драйвер.
Comment 8 Michael Shigorin 2007-05-24 18:38:05 MSD
Вопрос закрыт, Powerware 9120 с nut-2.0.5-alt2 (driver = bcmxcp) заработал после
выключения/включения UPS уже при подключенном serial cable.

[pw9120]
        port=/dev/ttyS0
        driver=bcmxcp
        baud_rate = 9600

Явное указание скорости понижает время service upsdrv start (при одном драйвере)
с 12.9 до 2 сек, но заводится в обоих случаях.

Надо будет посмотреть на alterator-nut повнимательней. :)
Comment 9 Alexander Volkov 2007-05-25 09:49:26 MSD
(In reply to comment #8)
> Вопрос закрыт, Powerware 9120 с nut-2.0.5-alt2 (driver = bcmxcp) заработал 
после
> выключения/включения UPS уже при подключенном serial cable.
> 
> [pw9120]
>         port=/dev/ttyS0
>         driver=bcmxcp
>         baud_rate = 9600
> 
> Явное указание скорости понижает время service upsdrv start (при одном 
драйвере)
> с 12.9 до 2 сек, но заводится в обоих случаях.
> 
> Надо будет посмотреть на alterator-nut повнимательней. :)
у меня 
[PW9120]
    driver = bcmxcp
    port   = /dev/ttyS0
    desc   = "Powerware UPS model 9120"

и все работает.
Comment 10 Michael Shigorin 2007-05-26 14:51:32 MSD
(In reply to comment #9)
> > Вопрос закрыт, Powerware 9120 с nut-2.0.5-alt2 (driver = bcmxcp) заработал 
> > после выключения/включения UPS уже при подключенном serial cable.
[...]
> и все работает.
У меня уже тоже. :)  Просто в документации бесперебойника этот момент с
подключением не описан.

Кстати, железка правильная как минимум в отношении power races, описанных в
документации nut -- на них не наступает. :)